Albuquerque Bernalillo County Water Utility Authority

Water Quality Report 2018

Distribution Zone 4

Definitions & Terms Notes & Sources of Substances

Regulatory Compliance Monitoring at EPTDS

Metals Sample
Collection
Years
Units Detection Zone 4 City-Wide Maximum
Contaminant
Level (MCL)
MCL Goal
Arsenic 2017 PPB Average
Range
6 2
0-9
10 0
Barium 2017 PPM Average
Range
0 0.0173
0-0.2
2 2
Chromium 2017 PPB Average
Range
0 1
0-7
100 100
Minerals
Fluoride 2017 PPM Average
Range
0.51 0.47
0.33-1.18
4 4
Nutrients
Nitrate 2018 PPM as N Average
Range
0 0.35
0-3.04
10 10
Organics
Total Xylenes 2017 PPM Average
Range
0 0.00002
0-0.00059
10 10
Radionuclides
Radium 226 + 228 2014 pCi/L Average
Range
0.03 0.18
0-0.41
15 15
Gross Alpha Particle Activity 2014 pCi/L Average
Range
0 0.7
0-2.5
15 15
Uranium 2014 PPB Average
Range
5 2
0-9
30 30

Voluntary Comprehensive Monitoring in Distribution

(Samples taken every three months, 2018 results)

Zone 4
Metals Units Minimum Average Maximum City Average MCL
Arsenic PPB 3 5 7 3 10 a
Chromium PPB 1 2 5 2 ~
Iron PPM 0 0.00154 0.0123 0.00447 0.3 a a
Minerals
Fluoride PPM 0.3 0.4 0.5 0.5 4 a
Nutrients
Nitrate PPM as N 0.1 0.26 0.4 0.41 10 a
General Chemistry
Alkalinity PPM as CaCO3 105 131 152 119 ~ a
Bicarbonate PPM as CaCO3 104 130 150 119 ~
Calcium PPM 36 43 54 52 ~ a
Chloride PPM 15 18 27 29 ~
Hardness grains/gallon 7.1 8.1 9.4 9 ~ a
Magnesium PPM 5.7 6.8 7.6 6.1 ~
Potassium PPM 3.3 5.1 7.2 3.5 ~ a
Silica PPM as SiO2 54 57 59 35 ~
Sodium PPM 26 35 44 31 ~ a
Sulfate PPM 52 64 71 71 ~
Total Dissolved Solids PPM 258 303 324 304 500 a a
Conductance micromhos/cm 401 451 494 486 ~
Free Chlorine Residual PPM 0.2 0.6 0.8 0.8 ~ a
pH Standard Units 7.7 7.9 8.2 7.7 ~
Temperature Fahrenheit 49 66 76 66 ~ a

a -

Represents the USEPA Secondary Maximum Contaminant Level (SMCL). Secondary Drinking Water Standards are unenforceable federal guidelines regarding taste, odor, color and certain other non-aesthetic effects of drinking water. USEPA recommends them as reasonable goals, but federal law does not require water systems to comply with them.