Albuquerque Bernalillo County Water Utility Authority

Water Quality Report 2018

Distribution Zone 13

Definitions & Terms Notes & Sources of Substances

Regulatory Compliance Monitoring at EPTDS

Metals Sample
Collection
Years
Units Detection Zone 13 City-Wide Maximum
Contaminant
Level (MCL)
MCL Goal
Arsenic 2017 PPB Average
Range
0 2
0-9
10 0
Barium 2017 PPM Average
Range
0 0.0173
0-0.2
2 2
Chromium 2017 PPB Average
Range
0 1
0-7
100 100
Minerals
Fluoride 2017 PPM Average
Range
0.39 0.47
0.33-1.18
4 4
Nutrients
Nitrate 2018 PPM as N Average
Range
0.16 0.35
0-3.04
10 10
Organics
Total Xylenes 2017 PPM Average
Range
0 0.00002
0-0.00059
10 10
Radionuclides
Radium 226 + 228 2017 pCi/L Average
Range
0.41 0.18
0-0.41
15 15
Gross Alpha Particle Activity 2017 pCi/L Average
Range
0 0.7
0-2.5
15 15
Uranium 2017 PPB Average
Range
0 2
0-9
30 30

Voluntary Comprehensive Monitoring in Distribution

(Samples taken every three months, 2018 results)

Zone 13
Metals Units Minimum Average Maximum City Average MCL
Arsenic PPB 0 4 6 3 10 a
Chromium PPB 0 2 3 2 ~
Iron PPM 0 0 0 0.00447 0.3 a a
Minerals
Fluoride PPM 0.2 0.4 0.7 0.5 4 a
Nutrients
Nitrate PPM as N 0.1 0.28 0.6 0.41 10 a
General Chemistry
Alkalinity PPM as CaCO3 97 116 133 119 ~ a
Bicarbonate PPM as CaCO3 97 116 132 119 ~
Calcium PPM 41 55 73 52 ~ a
Chloride PPM 14 25 42 29 ~
Hardness grains/gallon 7.4 9.5 12.3 9 ~ a
Magnesium PPM 5.8 6.5 7.2 6.1 ~
Potassium PPM 2.8 3.7 5.9 3.5 ~ a
Silica PPM as SiO2 21 36 50 35 ~
Sodium PPM 23 28 34 31 ~ a
Sulfate PPM 56 77 108 71 ~
Total Dissolved Solids PPM 290 320 384 304 500 a a
Conductance micromhos/cm 398 496 617 486 ~
Free Chlorine Residual PPM 0.6 0.9 1.1 0.8 ~ a
pH Standard Units 7.4 7.6 7.9 7.7 ~
Temperature Fahrenheit 47 64 83 66 ~ a

a -

Represents the USEPA Secondary Maximum Contaminant Level (SMCL). Secondary Drinking Water Standards are unenforceable federal guidelines regarding taste, odor, color and certain other non-aesthetic effects of drinking water. USEPA recommends them as reasonable goals, but federal law does not require water systems to comply with them.