Metals Sample
Collection
Years
Units Detection Zone 3 City-Wide Maximum
Contaminant
Level (MCL)
MCL Goal
Arsenic 2017 PPB Average
Range
6 2
0-9
10 0
Barium 2017 PPM Average
Range
0.1 0
0-0.2
2 2
Chromium 2017 PPB Average
Range
0 1
0-8
100 100
Minerals      
Fluoride 2017 PPM Average
Range
0.41 0.48
0.25-1.24
4 4
Nutrients      
Nitrate 2017 PPM as N Average
Range
0.1 0.38
0-2.99
10 10
Organics      
Total Xylenes 2017 PPM Average
Range
0 0.0001
0-0.0031
10 10
Radionuclides      
Radium 226 + 228 2017 pCi/L Average
Range
0.07 0.16
0-0.41
5 0
Gross Alpha Particle Activity 2017 pCi/L Average
Range
0.4 0.8
0-2.5
15 15
Uranium 2017 PPB Average
Range
4 2
0-9
30 30

Voluntary Comprehensive Monitoring in Distribution

(Samples taken every three months, 2017 results)

  Zone 3    
Metals Units Minimum Average Maximum City Average MCL
Arsenic PPB 0 2 4 2 10
Chromium PPB 0 1 2 1 100
Iron PPM 0 0.002 0.016 0.004 0.300 a
Minerals      
Fluoride PPM 0.25 0.35 0.45 0.37 4.0
Nutrients        
Nitrate PPM as N 0.14 0.25 0.43 0.33 10
General Chemistry      
Alkalinity PPM as CaCO3 86 102 116 97 ~
Bicarbonate PPM as CaCO3 85 101 115 97 ~
Calcium PPM 41 51 59 50 ~
Chloride PPM 25 38 48 33 250 a
Hardness grains/gallon 7.4 8.9 10.1 8.6 ~
Magnesium PPM 5.3 6.1 6.7 5.5 ~
Potassium PPM 3.0 3.1 4.0 3.2 ~
Silica PPM as SiO2 23 28 37 27 ~
Sodium PPM 21 27 33 28 ~
Sulfate PPM 30 61 86 72 250 a
Total Dissolved Solids PPM 254 279 310 282 500 a
Conductance micromhos/cm 392 426 489 439 ~
Free Chlorine Residual PPM 0.6 0.8 1.2 0.8 ~
pH Standard Units 7.5 7.7 7.8 7.6 6.5-8.5 a
Temperature Fahrenheit 47 64 79 66 ~

a -

Represents the USEPA Secondary Maximum Contaminant Level (SMCL). Secondary Drinking Water Standards are unenforceable federal guidelines regarding taste, odor, color and certain other non-aesthetic effects of drinking water. USEPA recommends them as reasonable goals, but federal law does not require water systems to comply with them.