Albuquerque Bernalillo County Water Utility Authority

Water Quality Report 2017

Distribution Zone 19

Definitions & Terms    Notes & Sources of Substances

 

Regulatory Compliance Monitoring at EPTDS

Metals Sample
Collection
Years
Units Detection Zone 19 City-Wide Maximum
Contaminant
Level (MCL)
MCL Goal
Arsenic 2017 PPB Average
Range
2 2
0-9
10 0
Barium 2017 PPM Average
Range
0 0
0-0.2
2 2
Chromium 2017 PPB Average
Range
1 1
0-8
100 100
Minerals      
Fluoride 2017 PPM Average
Range
0.58 0.48
0.25-1.24
4 4
Nutrients      
Nitrate 2017 PPM as N Average
Range
0.33 0.38
0-2.99
10 10
Organics      
Total Xylenes 2017 PPM Average
Range
0.0016 0.0001
0-0.0031
10 10
Radionuclides      
Radium 226 + 228 2016-2017 pCi/L Average
Range
0.22 0.16
0-0.41
5 0
Gross Alpha Particle Activity 2016-2017 pCi/L Average
Range
0.2 0.8
0-2.5
15 15
Uranium 2016-2017 PPB Average
Range
1 2
0-9
30 30

Voluntary Comprehensive Monitoring in Distribution

(Samples taken every three months, 2017 results)

  Zone 19    
Metals Units Minimum Average Maximum City Average MCL
Arsenic PPB 0 1 7 2 10
Chromium PPB 0 1 2 1 100
Iron PPM 0 0.004 0.032 0.004 0.300 a
Minerals      
Fluoride PPM 0.18 0.33 0.78 0.37 4.0
Nutrients        
Nitrate PPM as N 0.10 0.22 0.53 0.33 10
General Chemistry      
Alkalinity PPM as CaCO3 71 92 133 97 ~
Bicarbonate PPM as CaCO3 71 92 132 97 ~
Calcium PPM 28 53 64 50 ~
Chloride PPM 20 34 41 33 250 a
Hardness grains/gallon 5.3 9.0 10.6 8.6 ~
Magnesium PPM 4.7 5.5 6.4 5.5 ~
Potassium PPM 2.0 2.9 6.0 3.2 ~
Silica PPM as SiO2 16 24 62 27 ~
Sodium PPM 17 26 68 28 ~
Sulfate PPM 68 77 92 72 250 a
Total Dissolved Solids PPM 258 281 320 282 500 a
Conductance micromhos/cm 372 432 482 439 ~
Free Chlorine Residual PPM 0.5 0.8 1.1 0.8 ~
pH Standard Units 7.4 7.6 8.0 7.6 6.5-8.5 a
Temperature Fahrenheit 53 68 90 66 ~

a -

Represents the USEPA Secondary Maximum Contaminant Level (SMCL). Secondary Drinking Water Standards are unenforceable federal guidelines regarding taste, odor, color and certain other non-aesthetic effects of drinking water. USEPA recommends them as reasonable goals, but federal law does not require water systems to comply with them.